| A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24) |
| A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior) |
| An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device. |
| An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions. |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. |
| An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. |
| A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server. |
| A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. |
| An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application. |
| Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. |
| A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0. |
| A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system accepts reboot in session from unauthenticated users, supporting a denial of service condition. |
| An improper access control vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an improper handling of the system configuration can allow an attacker to execute arbitrary code under the context of root. |
| A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials. |
| A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable). |
| A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account. |
| Schneider Electric StruxureWare Data Center Expert before 7.4.0 uses cleartext RAM storage for passwords, which might allow remote attackers to obtain sensitive information via unspecified vectors. |
| A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files. |
| A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database. |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to escape out of remote PowerSCADA Anywhere applications and launch other processes. |